Tapcensus

Lee County Utilities Authority

Community water system in Leesburg, Lee County, Georgia, serving 20,194 people from ground water. 3 rules violated in the past three years. Owned by local government.

People served 20,194 ground water
Rules violated, past 3 years 3 one rule can carry several violations
Unresolved 0 rules currently in violation, EPA data updated Oct 7, 2026
Quarters with violations 11 of the last 12 quarters

Quarterly compliance history

VQ3
2023
VQ4
2023
VQ1
2024
VQ2
2024
VQ3
2024
SQ4
2024
SQ1
2025
SQ2
2025
VQ3
2025
SQ4
2025
SQ1
2026
–Q2
2026
UQ3
2026
–No violation identified VViolation identified SSerious violator (EPA enforcement priority) UUndetermined Oldest quarter on the left. Quarters 1 to 12 are the twelve most recent official quarters at EPA's last data refresh; the 13th is the quarter in progress at that refresh, which EPA reports as undetermined.

Rules violated in the past three years

Jul to Sep 2023 to Jul to Sep 2026

Inorganic Chemicals

Maximum Contaminant Level Violation Health-based

4 violations, Apr 2025 to Jun 2026 · Fluoride · 4 measured values

EPA rule code 333 · 4 violations recorded, 4 health-based

Maximum Contaminant Level Violation, health-based: 4 violations, Apr 2025 to Jun 2026. A sample exceeded the maximum contaminant level EPA allows in drinking water.

Measured
Fluoride 7.2 MG/L

Limit 4 MG/L · Jan to Mar 2026

Fluoride 7.7 MG/L

Limit 4 MG/L · Oct to Dec 2025

Fluoride 7.5 MG/L

Limit 4 MG/L · Jul to Sep 2025

Fluoride 4.8 MG/L

Limit 4 MG/L · Apr to Jun 2025

Contaminant on the record: Fluoride.

Fluoride, health effects: Above 2 mg/L: dental fluorosis (mottling/pitting of tooth enamel) in children under 8. Above 4 mg/L: skeletal fluorosis (joint pain, increased bone density) after decades of exposure. Limit: 4 mg/L primary MCL; 2 mg/L secondary MCL (cosmetic)

Nitrate Rule

Monitoring and Reporting

1 violation, Jan 2023 to Dec 2023 · Nitrate-Nitrite (Combined)

EPA rule code 331 · 1 violation recorded

Monitoring and Reporting: 1 violation, Jan 2023 to Dec 2023. The system did not complete required monitoring, or did not report the results on time. This does not show that a contaminant was found.

Contaminant on the record: Nitrate-Nitrite (Combined).

Consumer Confidence Rule

Other Violation

2 violations, Oct 2022 to Sep 2025

EPA rule code 420 · 2 violations recorded

Other Violation: 2 violations, Oct 2022 to Sep 2025. A requirement other than monitoring, reporting, or a contaminant limit, such as public notice or the annual water quality report.

What the rule requires: Community water systems must deliver an annual water quality report (Consumer Confidence Report) to all customers by July 1, covering the previous year. It must list all detected contaminants, compare them to MCLs, identify source water, and include educational language about lead. A violation means the report was not delivered on time or was incomplete.

About this rule

Lead and copper at the tap

The 90th percentile of the tap samples the system collected in its latest monitoring period, against EPA's action level. Levels vary between homes.

Lead 0.0015 mg/L

Action level 0.015 mg/L · Jan 2022 to Dec 2024

About this data

Rules violated and the list above come from EPA's SDWIS violation records, one row per violation and contaminant, grouped by the rule each row belongs to. A violation counts when its non-compliance period ended on or after Jul 1, 2023, the start of the thirteen quarters ECHO's three-year figures cover, or is still open; it is unresolved when it was still open at EPA's data refresh on Oct 7, 2026. EPA's rule code 500, "Not Regulated", is left out, as in ECHO's counts. Each rule's violation count is EPA's, and one rule can carry several: a missed monitoring round for a group of contaminants is one violation per contaminant and period. Category names are EPA's violation categories.

ECHO's own summary count of rules violated agrees with this grouping for 98.8% of active systems nationally, and its count of rules being violated for 98.7%; where they differ, the figures here follow the rows listed.

A measured value shown with a rule is the sample result EPA recorded with that violation (SDWIS viol_measure), against the limit EPA recorded on the same row (state_mcl), both in EPA's unit as written; violations without a recorded value, such as missed monitoring, show none. Other measured contaminant levels are not part of this record; each system publishes them in its annual Consumer Confidence Report.

Lead and copper are the newest 90th-percentile results in EPA's SDWA data download (LCR_SAMPLES, codes PB90 and CU90): for each monitoring period a system reports the 90th-percentile value of its tap samples, which EPA compares with its action level of 0.015 mg/L for lead and 1.3 mg/L for copper (40 CFR 141.80). A result is not a measurement of any one tap.

Service area from EPA's Public Water System Service Area Boundaries dataset: Random Forest method, Federal agency. The system's location is the centre of the service area EPA publishes for the system.

Source: the U.S. EPA's Enforcement and Compliance History Online system (ECHO), which publishes the federal Safe Drinking Water Information System. EPA's terms and values are shown as published. The Georgia records are from EPA's data refresh of Oct 7, 2026; EPA refreshes this data quarterly, and states report to EPA with a lag of three to six months, so the newest violations may not appear yet.