Tapcensus

Temple

Community water system in Cotton County, Oklahoma, serving 1,146 people from surface water. 4 rules violated in the past three years. Owned by local government.

People served 1,146 surface water
Rules violated, past 3 years 4 one rule can carry several violations
Unresolved 0 rules still in violation, EPA data updated Oct 7, 2026
Quarters with violations 10 of the last 12 quarters

Quarterly compliance history

VQ3
2023
VQ4
2023
SQ1
2024
VQ2
2024
VQ3
2024
VQ4
2024
VQ1
2025
VQ2
2025
VQ3
2025
–Q4
2025
–Q1
2026
VQ2
2026
UQ3
2026
–No violation identified VViolation identified SSerious violator (EPA enforcement priority) UUndetermined Oldest quarter on the left. Quarters 1 to 12 are the twelve most recent official quarters at EPA's last data refresh; the 13th is the quarter in progress at that refresh, which EPA reports as undetermined.

Rules violated in the past three years

Jul to Sep 2023 to Jul to Sep 2026

Interim and Long Term 1 Enhanced Surface Water Treatment Rule

Monitoring and ReportingTreatment Technique Violation Health-based

2 violations, Aug 2023 to Oct 2025 · Interim Enhanced Surface Water Treatment Rule

EPA rule code 122 · 2 violations recorded, 1 health-based

Treatment Technique Violation, health-based: 1 violation, Aug 2023 to Aug 2023. The system did not carry out a required treatment process or corrective action.

Monitoring and Reporting: 1 violation, Jul 2025 to Oct 2025. The system did not complete required monitoring, or did not report the results on time. This does not show that a contaminant was found.

Contaminant on the record: Interim Enhanced Surface Water Treatment Rule.

Interim Enhanced Surface Water Treatment Rule, health effects: Violations indicate failure to meet treatment technique requirements that reduce exposure to Cryptosporidium, Giardia, and other microbial pathogens. Cryptosporidium poses the greatest risk to immunocompromised individuals, infants, and the elderly, and can cause severe or fatal illness in vulnerable populations. Limit: Treatment technique — no numeric MCL; compliance means meeting turbidity limits (0.3 NTU in 95% of monthly samples) and Cryptosporidium removal benchmarks

Stage 1 Disinfectants and Disinfection Byproducts Rule

Monitoring and ReportingTreatment Technique Violation Health-based

7 violations, Oct 2023 to Oct 2025 · 3 contaminants

EPA rule code 210 · 7 violations recorded, 3 health-based

Treatment Technique Violation, health-based: 3 violations, Oct 2023 to Jun 2024. The system did not carry out a required treatment process or corrective action.

Monitoring and Reporting: 4 violations, Jan 2024 to Oct 2025. The system did not complete required monitoring, or did not report the results on time. This does not show that a contaminant was found.

Contaminants on the record: Chlorine (MRDL), Chlorine dioxide, Carbon, Total.

Chlorine (MRDL), health effects: Acute high-dose exposure to chlorinated water can cause eye and nose irritation, stomach discomfort, and nausea. Chronic exposure above the MRDL is primarily a concern because elevated chlorine accelerates formation of trihalomethanes and haloacetic acids, which are associated with increased cancer risk over time. Limit: MRDL: 4.0 mg/L as an annual average

Stage 2 Disinfectants and Disinfection Byproducts Rule

Maximum Contaminant Level ViolationMonitoring and Reporting Health-based

21 violations, Apr 2023 to Jun 2026 · TTHM (Total Trihalomethanes) · 16 measured values

EPA rule code 220 · 21 violations recorded, 16 health-based

Maximum Contaminant Level Violation, health-based: 16 violations, Jul 2023 to Jun 2025. A sample exceeded the maximum contaminant level EPA allows in drinking water.

Monitoring and Reporting: 5 violations, Apr 2023 to Jun 2026. The system did not complete required monitoring, or did not report the results on time. This does not show that a contaminant was found.

Measured
TTHM (Total Trihalomethanes) 0.082 MG/L

Limit 0.08 MG/L · Apr to Jun 2025

TTHM (Total Trihalomethanes) 0.095 MG/L

Limit 0.08 MG/L · Apr to Jun 2025

TTHM (Total Trihalomethanes) 0.109 MG/L

Limit 0.08 MG/L · Jan to Mar 2025

TTHM (Total Trihalomethanes) 0.094 MG/L

Limit 0.08 MG/L · Jan to Mar 2025

TTHM (Total Trihalomethanes) 0.082 MG/L

Limit 0.08 MG/L · Oct to Dec 2024

TTHM (Total Trihalomethanes) 0.092 MG/L

Limit 0.08 MG/L · Oct to Dec 2024

10 more in EPA's record

Contaminant on the record: TTHM (Total Trihalomethanes).

TTHM (Total Trihalomethanes), health effects: Long-term exposure is associated with increased bladder cancer risk. Some studies link high TTHM exposure to adverse reproductive outcomes. Bromodichloromethane is classified as a possible human carcinogen. Limit: 0.080 mg/L (80 ppb) locational running annual average (LRAA)

Lead and Copper Rule

Monitoring and Reporting

1 violation, Oct 2024 to Jul 2025

EPA rule code 350 · 1 violation recorded

Monitoring and Reporting: 1 violation, Oct 2024 to Jul 2025. The system did not complete required monitoring, or did not report the results on time. This does not show that a contaminant was found.

What the rule requires: The 1991 LCR uses action levels rather than MCLs: if the 90th percentile of high-risk tap samples exceeds 15 ppb lead or 1.3 mg/L copper, the system must take escalating corrective actions. Violations typically indicate failure to maintain adequate corrosion control — the treatment that keeps lead from leaching out of pipes, solder, and fixtures.

About this rule

Lead and copper at the tap

The 90th percentile of the tap samples the system collected in its latest monitoring period, against EPA's action level. Levels vary between homes.

Lead 0 mg/L

Action level 0.015 mg/L · Jan to Jun 2026

About this data

Rules violated and the list above come from EPA's SDWIS violation records, one row per violation and contaminant, grouped by the rule each row belongs to. A violation counts when its non-compliance period ended on or after Jul 1, 2023, the start of the thirteen quarters ECHO's three-year figures cover, or is still open; it is unresolved when it was still open at EPA's data refresh on Oct 7, 2026. EPA's rule code 500, "Not Regulated", is left out, as in ECHO's counts. Each rule's violation count is EPA's, and one rule can carry several: a missed monitoring round for a group of contaminants is one violation per contaminant and period. Category names are EPA's violation categories.

ECHO's own summary count of rules violated agrees with this grouping for 98.8% of active systems nationally, and its count of rules being violated for 98.7%; where they differ, the figures here follow the rows listed.

A measured value shown with a rule is the sample result EPA recorded with that violation (SDWIS viol_measure), against the limit EPA recorded on the same row (state_mcl), both in EPA's unit as written; violations without a recorded value, such as missed monitoring, show none. Other measured contaminant levels are not part of this record; each system publishes them in its annual Consumer Confidence Report.

Lead and copper are the newest 90th-percentile results in EPA's SDWA data download (LCR_SAMPLES, codes PB90 and CU90), retrieved on Oct 12, 2026: for each monitoring period a system reports the 90th-percentile value of its tap samples, which EPA compares with its action level of 0.015 mg/L for lead and 1.3 mg/L for copper (40 CFR 141.80). A result is not a measurement of any one tap.

Service area from EPA's Public Water System Service Area Boundaries dataset: State agency. The system's location is the centre of the service area EPA publishes for the system.

Source: the U.S. EPA's Enforcement and Compliance History Online system (ECHO), which publishes the federal Safe Drinking Water Information System. EPA's terms and values are shown as published. The Oklahoma records are from EPA's data refresh of Oct 7, 2026; EPA refreshes this data quarterly, and states report to EPA with a lag of three to six months, so the newest violations may not appear yet. Retrieved from ECHO on Oct 11, 2026.