Tapcensus

Northstar Mobile Home Park

Community water system in Larimer County, Colorado, serving 136 people from surface water purchased. 4 rules violated in the past three years, 1 still unresolved. Privately owned.

People served 136 surface water purchased
Rules violated, past 3 years 4 one rule can carry several violations
Unresolved 1 rules still in violation, EPA data updated Oct 7, 2026
Quarters with violations 2 of the last 12 quarters

Quarterly compliance history

–Q4
2023
–Q1
2024
–Q2
2024
–Q3
2024
–Q4
2024
–Q1
2025
–Q2
2025
–Q3
2025
–Q4
2025
–Q1
2026
VQ2
2026
–Q3
2026
VQ4
2026
–No violation identified VViolation identified SSerious violator (EPA enforcement priority) UUndetermined Oldest quarter on the left. Quarters 1 to 12 are the twelve most recently completed quarters at EPA's last data refresh; the 13th is the current quarter up to that date, which EPA reports as undetermined.

Still in violation

EPA data updated Oct 7, 2026

Lead and Copper Rule (LCR)

The 1991 LCR uses action levels rather than MCLs: if the 90th percentile of high-risk tap samples exceeds 15 ppb lead or 1.3 mg/L copper, the system must take…

EPA rule code 5000 · Treatment Technique

What it means: The 1991 LCR uses action levels rather than MCLs: if the 90th percentile of high-risk tap samples exceeds 15 ppb lead or 1.3 mg/L copper, the system must take escalating corrective actions. Violations typically indicate failure to maintain adequate corrosion control — the treatment that keeps lead from leaching out of pipes, solder, and fixtures.

Health effects: Lead: no safe level for children. Causes irreversible neurological damage, impaired cognitive development, behavioral problems, and reduced IQ in children under 6. In adults: hypertension, cardiovascular disease, kidney damage. Copper: acute gastrointestinal distress at high levels; liver/kidney damage at very high chronic levels.

Limit: Action levels: lead 15 ppb, copper 1.3 mg/L — 90th percentile of tap samples at high-risk sites

About this rule

Also violated in the past three years

Oct to Dec 2023 to Oct to Dec 2026

Chlorine (MRDL)

This entry tracks violations of the Maximum Residual Disinfectant Level (MRDL) for chlorine — meaning too much disinfectant residual in the distribution…

EPA rule code 0999 · Treatment Technique

What it means: This entry tracks violations of the Maximum Residual Disinfectant Level (MRDL) for chlorine — meaning too much disinfectant residual in the distribution system, not too little. Chlorine is added to water to kill pathogens, but excess residual can react with organic matter to form disinfection byproducts.

Health effects: Acute high-dose exposure to chlorinated water can cause eye and nose irritation, stomach discomfort, and nausea. Chronic exposure above the MRDL is primarily a concern because elevated chlorine accelerates formation of trihalomethanes and haloacetic acids, which are associated with increased cancer risk over time.

Limit: MRDL: 4.0 mg/L as an annual average

About this rule

Revised Total Coliform Rule (RTCR)

The 2013 RTCR (effective 2016) replaced the original TCR.

EPA rule code 8000 · Microbial

What it means: The 2013 RTCR (effective 2016) replaced the original TCR. It triggers automatic E. coli testing whenever total coliform is found. A single E. coli-positive sample is an acute MCL violation. It also requires systems exceeding 5% total coliform-positive samples to conduct a formal assessment and correct any deficiencies, helping prevent contamination before it escalates.

Health effects: Total coliform bacteria indicate that the disinfection barrier has been breached or fecal contamination is entering the system. E. coli specifically indicates fecal contamination and the possible presence of disease-causing pathogens (norovirus, Salmonella, Shigella, Campylobacter). Illness can be severe in elderly, young children, and immunocompromised individuals.

Limit: Zero E. coli; ≤5% of monthly samples total coliform-positive

About this contaminant

Surface Water Treatment Rule (SWTR)

All systems using surface water (rivers, lakes, reservoirs) or groundwater under surface influence (GWUDI) must filter and disinfect.

EPA rule code 0200 · Treatment Technique

What it means: All systems using surface water (rivers, lakes, reservoirs) or groundwater under surface influence (GWUDI) must filter and disinfect. Treatment technique violations mean the system failed to maintain adequate disinfectant residual, exceeded turbidity limits, or lacked required permits. Snowmelt and storm events can raise turbidity and pathogen loads in surface water.

Health effects: Without proper filtration/disinfection: Giardia lamblia (severe diarrhea, cramping), Cryptosporidium (life-threatening for immunocompromised individuals), viruses (hepatitis A, norovirus). Turbidity itself is not a health risk but can shield pathogens from disinfection.

Limit: Treatment technique: turbidity ≤0.3 NTU in 95% of monthly samples; detectable disinfectant residual in 95% of distribution samples

About this rule
About this data

EPA counts the rules a system was in violation of, not the individual violations; one rule can carry several in the same period. Unresolved means still in violation at EPA's latest data refresh. Measured contaminant levels are not part of this record; each system publishes them in its annual Consumer Confidence Report.

Source: the U.S. EPA's Enforcement and Compliance History Online system (ECHO), which publishes the federal Safe Drinking Water Information System. EPA's terms and values are shown as published. The Colorado records are from EPA's data refresh of Oct 7, 2026; EPA refreshes this data quarterly, and states report to EPA with a lag of three to six months, so the newest violations may not appear yet. Retrieved from ECHO on Oct 11, 2026.