Community water system in Concho County, Texas, serving 3,987 people from surface water. 5 rules violated in the past three years, 2 still unresolved. Owned by local government.

People served 3,987 surface water
Rules violated, past 3 years 5 one rule can carry several violations
Unresolved 2 rules currently in violation, EPA data updated Oct 7, 2026
Quarters with violations 12 of the last 12 quarters

Quarterly compliance history

SQ3
2023
SQ4
2023
VQ1
2024
SQ2
2024
VQ3
2024
VQ4
2024
SQ1
2025
SQ2
2025
SQ3
2025
SQ4
2025
SQ1
2026
SQ2
2026
UQ3
2026
–No violation identified VViolation identified SSerious violator (EPA enforcement priority) UUndetermined Oldest quarter on the left. Quarters 1 to 12 are the twelve most recent official quarters at EPA's last data refresh; the 13th is the quarter in progress at that refresh, which EPA reports as undetermined.

Currently in violation

EPA data updated Oct 7, 2026

Lead and Copper Rule

Monitoring and ReportingTreatment Technique Violation Health-based

5 violations, Oct 2023 to open

EPA rule code 350 · 5 violations recorded, 2 still open, 2 health-based

Treatment Technique Violation, health-based: 2 violations, open since Mar 2025. The system did not carry out a required treatment process or corrective action.

Monitoring and Reporting: 3 violations, Oct 2023 to Dec 2025. The system did not complete required monitoring, or did not report the results on time. This does not show that a contaminant was found.

What the rule requires: The 1991 LCR uses action levels rather than MCLs: if the 90th percentile of high-risk tap samples exceeds 15 ppb lead or 1.3 mg/L copper, the system must take escalating corrective actions. Violations typically indicate failure to maintain adequate corrosion control — the treatment that keeps lead from leaching out of pipes, solder, and fixtures.

Health effects: Lead: no safe level for children. Causes irreversible neurological damage, impaired cognitive development, behavioral problems, and reduced IQ in children under 6. In adults: hypertension, cardiovascular disease, kidney damage. Copper: acute gastrointestinal distress at high levels; liver/kidney damage at very high chronic levels. Limit: Action levels: lead 15 ppb, copper 1.3 mg/L — 90th percentile of tap samples at high-risk sites

About this rule

Public Notice Rule and Revised PN Rule

Other Violation

6 violations, Oct 2014 to open · Public Notification Rule

EPA rule code 410 · 6 violations recorded, 4 still open

Other Violation: 6 violations, 4 still open, Oct 2014 to open. A requirement other than monitoring, reporting, or a contaminant limit, such as public notice or the annual water quality report.

Contaminant on the record: Public Notification Rule.

Also violated in the past three years

Jul to Sep 2023 to Jul to Sep 2026

Stage 2 Disinfectants and Disinfection Byproducts Rule

Maximum Contaminant Level Violation Health-based

20 violations, Jul 2023 to Jun 2026 · 2 contaminants · 20 measured values

EPA rule code 220 · 20 violations recorded, 20 health-based

Maximum Contaminant Level Violation, health-based: 20 violations, Jul 2023 to Jun 2026. A sample exceeded the maximum contaminant level EPA allows in drinking water.

Measured
TTHM (Total Trihalomethanes) 0.335 MG/L

Limit 0.08 MG/L · Apr to Jun 2026

Total Haloacetic Acids (HAA5) 0.088 MG/L

Limit 0.06 MG/L · Apr to Jun 2026

TTHM (Total Trihalomethanes) 0.375 MG/L

Limit 0.08 MG/L · Jan to Mar 2026

Total Haloacetic Acids (HAA5) 0.086 MG/L

Limit 0.06 MG/L · Jan to Mar 2026

TTHM (Total Trihalomethanes) 0.406 MG/L

Limit 0.08 MG/L · Oct to Dec 2025

Total Haloacetic Acids (HAA5) 0.089 MG/L

Limit 0.06 MG/L · Oct to Dec 2025

14 more in EPA's record

Contaminants on the record: Total Haloacetic Acids (HAA5), TTHM (Total Trihalomethanes).

Total Haloacetic Acids (HAA5), health effects: Dichloroacetic acid is a probable human carcinogen (Group B2). Long-term exposure to trichloroacetic acid may also increase cancer risk. Animal studies show liver, kidney, and reproductive effects at high doses. Limit: 0.060 mg/L (60 ppb) locational running annual average (LRAA)

TTHM (Total Trihalomethanes), health effects: Long-term exposure is associated with increased bladder cancer risk. Some studies link high TTHM exposure to adverse reproductive outcomes. Bromodichloromethane is classified as a possible human carcinogen. Limit: 0.080 mg/L (80 ppb) locational running annual average (LRAA)

Radionuclides and Revised Rad Rule

Maximum Contaminant Level Violation Health-based

20 violations, Jul 2023 to Mar 2026 · 2 contaminants · 20 measured values

EPA rule code 340 · 20 violations recorded, 20 health-based

Maximum Contaminant Level Violation, health-based: 20 violations, Jul 2023 to Mar 2026. A sample exceeded the maximum contaminant level EPA allows in drinking water.

Measured
Combined Radium (-226 and -228) 66 PCI/L

Limit 5 PCI/L · Jan to Mar 2026

Gross Alpha, Excl. Radon and U 93 PCI/L

Limit 15 PCI/L · Jan to Mar 2026

Combined Radium (-226 and -228) 63 PCI/L

Limit 5 PCI/L · Oct to Dec 2025

Gross Alpha, Excl. Radon and U 105 PCI/L

Limit 15 PCI/L · Oct to Dec 2025

Combined Radium (-226 and -228) 64 PCI/L

Limit 5 PCI/L · Jul to Sep 2025

Gross Alpha, Excl. Radon and U 105 PCI/L

Limit 15 PCI/L · Jul to Sep 2025

14 more in EPA's record

Contaminants on the record: Gross Alpha, Excl. Radon and U, Combined Radium (-226 and -228).

Gross Alpha, Excl. Radon and U, health effects: Alpha-emitting radionuclides accumulate in bone and soft tissue, delivering sustained internal radiation doses that increase lifetime cancer risk. There is no established safe threshold for ionizing radiation. Individual contributors such as radium-226 and polonium-210 have their own MCLs; gross alpha serves as a cost-effective screening tool that triggers more specific radionuclide analysis when exceeded. Limit: 15 pCi/L (excluding radon and uranium)

Combined Radium (-226 and -228), health effects: Radium is a bone-seeking radionuclide that accumulates in skeletal tissue after ingestion. Long-term exposure increases the risk of bone cancer and leukemia. There is no safe threshold for ionizing radiation — the MCL is set at a level balancing risk reduction with treatment feasibility. Children are particularly vulnerable due to higher rates of bone growth and calcium uptake. Limit: 5 pCi/L (combined Ra-226 and Ra-228)

Lead and Copper Rule Revisions

Reporting Violation

1 violation, Jul 2025 to Jan 2026

EPA rule code 351 · 1 violation recorded

Reporting Violation: 1 violation, Jul 2025 to Jan 2026. The system did not report required information on time.

What the rule requires: The 2021 LCRR updated the 1991 LCR with mandatory lead service line inventories and replacement planning, a new 'trigger level' at 10 ppb requiring optimization, and strengthened public education. The 2024 Lead and Copper Rule Improvements (LCRI) further requires replacing all lead service lines within 10 years.

About this rule

Lead and copper at the tap

The 90th percentile of the tap samples the system collected in its latest monitoring period, against EPA's action level. Levels vary between homes.

Lead 0.0223 mg/L

Action level 0.015 mg/L · Jan to Jun 2026

About this data

Rules violated and the list above come from EPA's SDWIS violation records, one row per violation and contaminant, grouped by the rule each row belongs to. A violation counts when its non-compliance period ended on or after Jul 1, 2023, the start of the thirteen quarters ECHO's three-year figures cover, or is still open; it is unresolved when it was still open at EPA's data refresh on Oct 7, 2026. EPA's rule code 500, "Not Regulated", is left out, as in ECHO's counts. Each rule's violation count is EPA's, and one rule can carry several: a missed monitoring round for a group of contaminants is one violation per contaminant and period. Category names are EPA's violation categories.

ECHO's own summary count of rules violated agrees with this grouping for 98.8% of active systems nationally, and its count of rules being violated for 98.7%; where they differ, the figures here follow the rows listed.

A measured value shown with a rule is the sample result EPA recorded with that violation (SDWIS viol_measure), against the limit EPA recorded on the same row (state_mcl), both in EPA's unit as written; violations without a recorded value, such as missed monitoring, show none. Other measured contaminant levels are not part of this record; each system publishes them in its annual Consumer Confidence Report.

Lead and copper are the newest 90th-percentile results in EPA's SDWA data download (LCR_SAMPLES, codes PB90 and CU90): for each monitoring period a system reports the 90th-percentile value of its tap samples, which EPA compares with its action level of 0.015 mg/L for lead and 1.3 mg/L for copper (40 CFR 141.80). A result is not a measurement of any one tap.

Service area from EPA's Public Water System Service Area Boundaries dataset: State Agency. The system's location is the centre of the service area EPA publishes for the system.

Source: the U.S. EPA's Enforcement and Compliance History Online system (ECHO), which publishes the federal Safe Drinking Water Information System. EPA's terms and values are shown as published. The Texas records are from EPA's data refresh of Oct 7, 2026; EPA refreshes this data quarterly, and states report to EPA with a lag of three to six months, so the newest violations may not appear yet.